10.5 Motion Parameter Details
10.5.2 Setting Parameter List
10-38
OW0C
Output Data
Option
Selection
Bit 0: Torque Compensa-
tion (Option)
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the output data
option Torque Compensation (OW13) will be
enabled when the Inverter Drive Control command
is executed.
Bit 1: Analog Output Ter-
minal 1 Output
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the output data
option Analog Output Terminal 1 Output
(OW14) will be enabled when the Inverter
Drive Control command is executed.
Bit 2: Analog Output Ter-
minal 2 Output
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the output data
option Analog Output Terminal 2 Output
(OW15) will be enabled when the Inverter
Drive Control command is executed.
Bit 3: Terminal Output
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the output data
option Terminal Output (OW16) will be
enabled when the Inverter Drive Control command
is executed.
Bit 4: PID Target
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the output data
option PID Target (OW17) will be enabled
when the Inverter Drive Control command is exe-
cuted.
Bit 5: Pulse Train Output
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the output data
option Pulse Train Output (OW18) will be
enabled when the Inverter Drive Control command
is executed.
Bit 6: V/f Gain
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the output data
option V/f Gain (OW19) will be enabled when
the Inverter Drive Control command is executed.
Bit 7 Reserved
Bit 8: Command Selec-
tion
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the output data
option Command Selection (OW1B) will be
enabled when the Inverter Drive Control command
is executed.
Bits 9 to F Reserved
OW
0D
Input Data
Option
Selection
Bit 0: Motor Speed
(Option)
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Motor Speed (IW13) will be monitored
when the Inverter Drive Control command is exe-
cuted.
Bit 1: Torque Reference
Setting
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Torque Reference (IW14) will be moni-
tored when the Inverter Drive Control command is
executed.
Bit 2: Encoder Count
PG1
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Encoder Count PG1 (IW15) will be
monitored when the Inverter Drive Control com-
mand is executed.
Bit 3: Frequency
Reference (Option)
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Frequency Reference (IW16) will be
monitored when the Inverter Drive Control com-
mand is executed.
Continued on next page.
Continued from previous page.
Register No. Name Description