10.5 Motion Parameter Details
10.5.2 Setting Parameter List
10
Inverter Operation
10-39
OW0D
Input Data
Option
Selection
(continued)
Bit 4: Analog Input A2
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Analog Input A2 (IW17) will be moni-
tored when the Inverter Drive Control command is
executed.
Bit 5: Main Bus Voltage
(Option)
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Main Bus Voltage (IW18) will be moni-
tored when the Inverter Drive Control command is
executed.
Bit 6: Alarm Code
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Alarm Code (IW19) will be monitored
when the Inverter Drive Control command is exe-
cuted.
Bit 7: Warning Code
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Warning Code (IW1A) will be moni-
tored when the Inverter Drive Control command is
executed.
Bit 8: Multi-Function
Output Terminal
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Multi-Function Output Terminal (IW1B)
will be monitored when the Inverter Drive Control
command is executed.
Bit 9: Analog Input A3
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Analog Input A3 (IW1C) will be moni-
tored when the Inverter Drive Control command is
executed.
Bit A: Multi-Function
Input Terminal
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Multi-Function Input Terminal (IW1D)
will be monitored when the Inverter Drive Control
command is executed.
Bit B: Analog Input A1
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Analog Input A1 (IW1E) will be moni-
tored when the Inverter Drive Control command is
executed.
Bit C: Encoder Count
PG2
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Encoder Count PG2 (IW1F) will be
monitored when the Inverter Drive Control com-
mand is executed.
Bit D: Monitor data set in
F6-23
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Monitor Data Set in F6-23 (IW20) will
be monitored when the Inverter Drive Control com-
mand is executed.
Bit E: Monitor data set in
F6-24
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Monitor Data Set in F6-24 (IW21) will
be monitored when the Inverter Drive Control com-
mand is
executed.
Bit F Reserved
Contin
ued on next page.
Continued from previous page.
Register No. Name Description