10.5 Motion Parameter Details
10.5.2 Setting Parameter List
10-41
OW0F
Auxiliary
Input Data
Option
Selection
Bit 0: Motor Speed
(Option)
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Motor Speed (IW13) will be monitored
when the Inverter I/O Control subcommand is exe-
cuted.
Bit 1: Torque Reference
Setting
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Torque Reference (IW14) will be moni-
tored when the Inverter I/O Control subcommand is
executed.
Bit 2: Encoder Count
PG1
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Encoder Count PG1 (IW15) will be
monitored when the Inverter I/O Control subcom-
mand is executed.
Bit 3 Frequency Refer-
ence (Option)
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Frequency Reference (IW16) will be
monitored when the Inverter I/O Control subcom-
mand is executed.
Bit 4: Analog Input A2
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Analog Input A2 (IW17) will be moni-
tored when the Inverter I/O Control subcommand is
executed.
Bit 5: Main Bus Voltage
(Option)
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Main Bus Voltage (IW18) will be moni-
tored when the Inverter I/O Control subcommand is
executed.
Bit 6: Alarm Code
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Alarm Code (IW19) will be monitored
when the Inverter I/O Control subcommand is exe-
cuted.
Bit 7: Warning Code
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Warning Code (IW1A) will be moni-
tored when the Inverter I/O Control subcommand is
executed.
Bit 8: Multi-Function
Output Terminal
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Multi-Function Output Terminal (IW1B)
will be monitored when the Inverter I/O Control sub-
command is executed.
Bit 9: Analog Input A3
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Analog Input A3 (IW1C) will be moni-
tored when the Inverter I/O Control subcommand is
executed.
Bit A: Multi-Function
Input Terminal
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Multi-Function Input Terminal (IW1D)
will be monitored when the Inverter I/O Control sub-
command is executed.
Bit B: Analog Input A1
0: Disabled, 1: Enabled
When this bit is set to 1 (enabled), the input data
option Analog Input A1 (IW1E) will
be moni-
tore
d when the Inverter I/O Control subcommand is
executed.
Continued on next page.
Continued from previous page.
Register No. Name Description