No. Bit/Name/Value/
Bit Name Value Information
(continued)
8 SPEED2 ACT 1 Speed2 (parameter 80.17) is the current speed reference used
by the lift.
0 Speed 2 (parameter 80.17) is not the current speed reference
used by the lift.
9 SPEED3 ACT 1 Speed3 (parameter 80.18) is the current speed reference used
by the lift.
0 Speed3 (parameter 80.18) is not the current speed reference
used by the lift.
10 RDY CLS
SPLYCONT
1
Ready to close the supply contactor. Safe torque off
function is inactive.
0
Not ready to close the supply contactor. Safe torque off
function is active.
11 INSPECT MODE
SEL
1
Inspection mode is activated with parameter 10.84
INSPECTION MODE.
0
Inspection mode is not active.
12 EVAC MODE ACT 1
Evacuation mode is activated with parameter 10.81
EVACUATION MODE.
0
Evacuation mode is not active.
13 TORQ PRV OK 1
Torque proving is successful.
0
Torque proving was not successful during previous start
attempt.
14 JOGGING
ACTIVE
1
Drive jogging mode is active.
0
Drive jogging mode is not active.
15 LVL TIME OVER 1
Leveling overtime stop function is activated during the
last run.
0
Leveling overtime stop function is not active.