Parameters 265
80.14 MEDIUM SPEED
Defines the speed reference to be used in the normal
travel mode when the bit combination of parameters
80.06, 80.07 and 80.08 is 010. This is an additional
speed reference which can be defined to be used
instead of the nominal speed based on the floor
distance.
0.50 m/s /
Real
0.00…25.00 m/s Medium speed reference. 100 = 1 m/s
80.15 INSPECTION
SPEED
Defines the speed reference to be used when the
inspection mode is enabled with parameter 10.84
INSPECTION MODE. If the inspection mode is not in
use, this speed reference can also be defined to be
used in the normal travel mode when the bit
combination of parameters 80.06, 80.07 and 80.08 is
101.
0.25 m/s /
Real
0.00…25.00 m/s Inspection speed reference. 100 = 1 m/s
80.16 EVACUATION
SPEED
Defines the speed reference to be used when the
evacuation mode is enabled with parameter 10.81
EVACUATION MODE.
0.10 m/s /
Real
0.00…25.00 m/s Evacuation speed reference. 100 = 1 m/s
80.17 SPEED2
Defines the speed reference to be used in the normal
travel mode when the bit combination of parameters
80.06, 80.07 and 80.08 is 001. This is an additional
speed reference which can be defined to be used
instead of the nominal speed based on the floor
distance.
0.40 m/s /
Real
0.00…25.00 m/s Speed2. 100 = 1 m/s
80.18 SPEED3
Defines the speed reference to be used in the normal
travel mode when the bit combination of parameters
80.06, 80.07 and 80.08 is 001. This is an additional
speed reference which can be defined to be used
instead of the nominal speed based on the floor
distance.
0.60 m/s /
Real
0.00…25.00 m/s Speed3. 100 = 1 m/s
80.19 OFF DLY SPD LIM
Defines the lift speed limit for activating the extended
off-delay time periods defined with parameters 80.20
…80.23. The delay periods are used only when the
lift speed is lower than this limit.
0.00 m/s /
Real
0.00…25.00 m/s Off-delay speed limit. 100 = 1 m/s
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)