186 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
P445 Current Limitation Cycle Load Control
Enable
0 1000000000000 On/OffYY
P447Minimum Start Frequency During Time0 13.650000000000000sOfflineYY
P448Minimum Start Frequency 0 10000000000000%OfflineYY
P449 Low Speed Voltage Compensation
During Flux Building Process
0 3222222222222%OfflineYY
P451Low Speed Voltage Compensation0 3111111111111%OfflineYY
P452 Low Speed Voltage Compensation
Frequency Threshold
0 100 20 20 20 20 20 20 20 20 20 20 20 20 On/Off Y Y
P453V/F Curve 0 5555555555555 OfflineYY
P454Flux Time 0 102222222222 2sOffline Y
P455 Modulation Index 0.0 110.0 84.0 87.6 77.3 85.0 83.8 87.0 87.0 81.0 85.0 83.7 91.0 89.0 On/Off Y Y
P456 Motor Voltage Upper Limit 0.00 110.0 84.0 87.6 77.3 85.0 83.8 87.0 87.0 81.0 85.0 83.7 91.0 89.0 On/Off Y Y
P457 Flying Start Voltage Recovery Time (Low
Speed Region)
0.00 163.84 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 s On/Off Y Y
P458Coefficient A 0 100404040404040404040404040 Offline Y
P459 Flying Start Voltage Recovery Time (High
Speed Region)
0.00 163.84 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 s On/Off Y Y
P460 Rated Output Frequency 0 75 50 50 50 50 50 50 50 50 50 50 50 50 Offline Y Y
P461Restart Enable 0 1000000000000 On/OffYY
P462 Fault Reset Timeout 0.04 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 120.00 s On/Off Y
P463 Flying Start Low/High Speed Regions
Boundary
0 100 16 16 16 16 16 16 16 16 16 16 16 16 % On/Off Y Y
P465Power Cell Fault Auto Reset Delay0 10444444444444sOn/Off Y
P466 Maximum Output Frequency 0 75 50 50 50 50 50 50 50 50 50 50 50 50 Offline Y Y
P467Over Speed Enable 0 1000000000000 OfflineYY
P470Version Compatibility Enable 0 1111111111111 Offline Y
P471Fault-To-Bypass 0 1000000000000 OfflineYY
P472Fault-To-Bypass Delay 0 5333333333333 On/OffYY
P473 Fault-To-Bypass Delay When Starting
The Motor
0 60606060606060606060606060sOn/OffYY
P474Fault-To-Bypass Minimum Frequency0 75555555555555HzOfflineYY
P475Owner #1 Selection 0 1000000000000 On/OffYY
P476Owner #2 Selection 2 23888888888888 On/OffYY
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R