Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 59
Parameter Descriptions Chapter 2
K Number 252
Access Level: R&D
Read/Write: Read only
This register stores the value of the actual frequency. The unit is PU.
Motor Current HMI Display Address
Linear Number: P374
Default Value: 118
Minimum Value: 0
Maximum Value: 500
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the address for Motor Current HMI Display.
Power Display Enable
Linear Number: P479
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is used to enable or disable the display of output power and
energy values on the HMI.
Ramp Parameters
Deceleration Time
Linear Number: P399
Default Value: 400.0 s
Minimum Value: 0.0 s
Maximum Value: 3276.7 s
Access Level: User, Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Deceleration Time.
Value Description
0Disable
1Enable