88 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Fan Control Parameters
Fan Control Mode
Linear Number: P094
Default Value: 0
Minimum Value: 0
Maximum Value: 2
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is used to select the fan control mode.
Fan Control Group #1 Fan Number
Linear Number: P095
Default Value: 0
Minimum Value: 0
Maximum Value: 10
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the number of fans in transformer cabinet #1.
Fan Control Group #2 Fan Number
Linear Number: P096
Default Value: 0
Minimum Value: 0
Maximum Value: 10
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the number of fans in transformer cabinet #2.
Fan Control Group #3 Fan Number
Linear Number: P097
Default Value: 0
Minimum Value: 0
Maximum Value: 100
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the number of fans in the power cell cabinet.
Value Description
0 Non-redundant fan mode
1 One fan as redundant fan mode
2All fans in cycle mode