Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 33
Functional Descriptions Chapter 1
5. The controller starts the drive.
VFD to Bypass
This function is used switch the motor running mode from the drive to the 
frequency bypass.
During automatic bypass, one-drive-one-motor, when the VFD to Bypass 
function is enabled, regardless of whether the drive is in Local or Remote control 
mode, the drive will automatically set the frequency to the rated frequency and 
save the current value of Stop Method (P024). Then it will set the value of Stop 
Method to “1”, Motor Rotation Direction Under Local Control (P008) to “1”, and 
Motor Rotation Direction Command Selection (P009) to “0”. 
When the actual frequency is equal to the rated frequency the controller 
disconnects the drive contactor, then after the time set in Fault-To-Bypass (P472) 
has elapsed, closes the bypass contactor so that the motor starts running, and Stop 
Method is restored to its original value.
Current Limit
This function is used to prevent the motor from being overloaded for a long time, 
and to protect the motor and drive. When the motor is overloaded, the drive will 
ramp down until the output current RMS value is lower than the drive setting. 
This feature can also be used to limit the ramp up current.
For current limit, the over load time, over load extent, and over load period can be 
defined. This function can suppress current spikes which are caused by changes in 
transient load.
The following parameters are used for this function:
• Current Limitation Enable (P436)
• Current Limitation Enable Frequency Range Lower Limit (P438)
• Current Limitation Threshold (P441)
• Current Limitation Heating Time (P442)
• Current Limitation Cooling Time (P443)
• Current Limitation Decel Ramp Slope Change (P444)
• Current Limitation Cycle Load Control Enable (P445)
• Current Limit Loop Kp (P133)
After clicking the Bypass to VFD button and a delay of 60 seconds has passed, 
parameters Flying Start Mode and Restart Enable are restored to their original 
values.
After performing the Bypass to VFD function, there is a 60 second delay before 
you can perform the VFD to Bypass function or Reset operation. This is to 
prevent errors such as internal parameters not being restored, no response 
after clicking the VFD to Bypass button, and so on.