100 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Low Voltage Ride Through
Parameters
Low Voltage Ride Through Recovery Voltage Boost Coefficient
Linear Number: P280
Default Value: 0%
Minimum Value: 0%
Maximum Value: 100%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Low Voltage Ride Through Recovery Voltage Boost
Coefficient.
Low Voltage Ride Through Min Time Interval
Linear Number: P281
Default Value: 10 s
Minimum Value: 0 s
Maximum Value: 1000 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the minimum time interval for Low Voltage Ride Through.
Low Voltage Ride Through Min Frequency Limit
Linear Number: P282
Default Value: 5%
Minimum Value: 5%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the minimum frequency limit for Low Voltage Ride
Through.
Low Voltage Ride Through Enable
Linear Number: P283
Default Value: 1
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is used to enable or disable the Low Voltage Ride Through
function.
Value Description
0 Disable Low Voltage Ride Through
1 Enable Low Voltage Ride Through