128 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Deceleration and
Acceleration Process
Parameters
Deceleration Process Enable
Linear Number: P385
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is used to enable or disable the Deceleration Process function.
Deceleration Time 1
Linear Number: P386
Default Value: 150.0 s
Minimum Value: 1.0 s
Maximum Value: 3276.7 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Deceleration Time 1.
Deceleration Frequency 1
Linear Number: P387
Default Value: 30
Minimum Value: 0
Maximum Value: 75
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Deceleration Frequency 1.
Deceleration Time 2
Linear Number: P388
Default Value: 80.0 s
Minimum Value: 1.0 s
Maximum Value: 3276.7 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Deceleration Time 2.
Value Description
0 Disable Deceleration Process
1 Enable Deceleration Process

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals