Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 63
Parameter Descriptions Chapter 2
Stop Mode Parameters
Stop Method
Linear Number: P024
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Stop Method.
Frequency Command-Low Frequency Region Boundary
Linear Number: P251
Default Value: 0.5 pu
Minimum Value: 0.0 pu
Maximum Value: 100.0 pu
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Frequency Command-Low Frequency Region Boundary.
Motor In Stopping Condition Threshold
Linear Number: P252
Default Value: 1 pu
Minimum Value: 0 pu
Maximum Value: 100 pu
Access Level: Setup, R&D
Read/Write: Read/Write
Modify: Online/Offline
This parameter sets the Motor In Stopping Condition Threshold.
Motor Coast Stop Time
Linear Number: P253
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 10000 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Motor Coast Stop Time.
Value Description
0Ramp Down
1 Coast Stop

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals