Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 135
Parameter Descriptions Chapter 2
Protection Parameters
VFD Minimum Overload Current
Linear Number: P079
Default Value: 100.00%
Minimum Value: 0.00%
Maximum Value: 399.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the minimum overload current for the drive.
VFD Overload Current
Linear Number: P080
Default Value: 120.00%
Minimum Value: 0.00%
Maximum Value: 399.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the overload current threshold for the drive.
VFD Overload Time
Linear Number: P081
Default Value: 60 s
Minimum Value: 0 s
Maximum Value: 32767 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the overload time delay for the drive.
VFD Overload Cycle Time
Linear Number: P082
Default Value: 600 s
Minimum Value: 0 s
Maximum Value: 32767 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the heating and cooling cycles for the drive.