166 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Load Loss Control Parameters
Motor Auto-tune Parameters
P410 Flying Start Compensation Current
Threshold for Fast Compensation
0.00 399.99 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 60.00 On/Off Y
P416Flying Start Mode 0 3000000000000 On/OffYY
P417Flying Start Motor Speed Search Timeout0 1000505050505050505050505050s On/OffYY
P457 Flying Start Voltage Recovery Time (Low
Speed Region)
0.00 163.84 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 s On/Off Y Y
P459 Flying Start Voltage Recovery Time (High
Speed Region)
0.00 163.84 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 s On/Off Y Y
P463 Flying Start Low/High Speed Regions
Boundary
0 100 16 16 16 16 16 16 16 16 16 16 16 16 % On/Off Y Y
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
P045Load Loss Control Enable 0 1000000000000 On/OffYY
P046 Load Loss Enable Frequency 0 100 20 20 20 20 20 20 20 20 20 20 20 20 % On/Off Y Y
P047Load Loss Control Differential Scaling0 2000888888888888%On/Off Y
P048 Load Loss Frequency Compensation
Upper Limit
0 5555555555555%On/OffYY
P049Load Loss Control Scaling Factor0 2000000000000000%On/Off Y
P050Load Loss Control Integral Time 0 100000000000000msOn/Off Y
P051 Load Loss Control Filter Time 0 200 100 100 100 100 100 100 100 100 100 100 100 100 ms On/Off Y
P052 Load Loss Enable Current Threshold 0 100 10 10 10 10 10 10 10 10 10 10 10 10 % On/Off Y
P053 Load Loss Control Exit Delay 0 16000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 ms On/Off Y
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
P121Motor Autotune Selection 0 3000000000000 OfflineYY
P122 Motor Autotune Delay 0 32767 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 ms On/Off Y
P123 Motor Autotune Filter Time 0 32767 10 10 10 10 10 10 10 10 10 10 10 10 ms On/Off Y

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals