98 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Flux Control-Lag Band Width
Linear Number: P276
Default Value: 3
Minimum Value: 0
Maximum Value: 100
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the lag band width for flux control. It is used to trigger the
flux control function.
Derating Control Enable Threshold
Linear Number: P278
Default Value: 100.00%
Minimum Value: 50.00%
Maximum Value: 199.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold to enable the Derating Control function.
Derating Control Output Filter Time
Linear Number: P279
Default Value: 9.95 ms
Minimum Value: 9.95 ms
Maximum Value: 1999.94 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Derating Control Output Filter Time.
Voltage Loop Parameters
Voltage Loop Enable
Linear Number: P290
Default Value: 1
Minimum Value: 0
Maximum Value: 1
Access Level: R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is used to enable or disable the Voltage Loop function.
Value Description
0 Disable Voltage Loop
1 Enable Voltage Loop