Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 65
Parameter Descriptions Chapter 2
Switch Frequency Setting
Parameters
Switch Frequency Setting Enable Code
Linear Number: P087
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is used to enable or disable the Switch Frequency Setting Code.
Switch Frequency Setting
Linear Number: P088
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is used to select the frequency value for Switch Frequency
Setting.
VF Curve Setting Parameters
Slip Compensation Enable
Linear Number: P111
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is used to enable or disable Slip Compensation.
Value Description
0 Disable Switch Frequency Setting Code
1 Enable Switch Frequency Setting Code
Value Description
0 600 Hz
1 1200 Hz
Value Description
0 Disable Slip Compensation
1Enable Slip Compensation