Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 113
Parameter Descriptions Chapter 2
Current Stability Loop Frequency Range3 Output Scaling Factor
Linear Number: P071
Default Value: 0%
Minimum Value: 0%
Maximum Value: 100%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the scaling factor for Current Stability Loop Frequency
Range3 Output.
Current Stability Loop Enable Delay
Linear Number: P072
Default Value: 10
Minimum Value: 0
Maximum Value: 163
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Current Stability Loop Enable Delay time. The unit is
100 ms.
Flying Start Parameters
Flying Start-Initial Output Voltage
Linear Number: P113
Default Value: 8%
Minimum Value: 0%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the initial output voltage for Flying Start.
Flying Start-Current Comparison Delay For Motor Speed Search
Linear Number: P114
Default Value: 500 ms
Minimum Value: 0 ms
Maximum Value: 5000 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Flying Start-Current Comparison Delay for Motor Speed
Search.