EasyManuals Logo

Allen-Bradley PowerFlex 6000 Firmware, Parameters, And Troubleshooting Manual

Allen-Bradley PowerFlex 6000
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #114 background imageLoading...
Page #114 background image
114 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Flying Start-Current Threshold For Successful Motor Speed Search
Linear Number: P115
Default Value: 4.99 pu
Minimum Value: 0.00 pu
Maximum Value: 100.00 pu
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Flying Start-Current Threshold for successful Motor
Speed Search.
Flying Start Voltage Threshold
Linear Number: P187
Default Value: 3%
Minimum Value: 0%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Flying Start Voltage Threshold.
Flying Start Compensation Enable
Linear Number: P393
Default Value: 1
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is used to enable or disable Flying Start Compensation.
Flying Start Compensation Current Threshold
Linear Number: P394
Default Value: 50.00
Minimum Value: 0.00
Maximum Value: 399.99
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the Flying Start Compensation Current.
Value Description
0 Disable Flying Start Compensation
1 Enable Flying Start Compensation

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals