Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 61
Parameter Descriptions Chapter 2
Deceleration Time Unit
Linear Number: P406
Default Value: 0.1 s
Minimum Value: 0.01 s
Maximum Value: 0.1 s
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the unit value for Deceleration Time, either “0.01” or “0.1”
second. It is used to set the S Curve.
Amplification Coefficient Of Error Terms
Linear Number: P409
Default Value: 100.00%
Minimum Value: 0.00%
Maximum Value: 199.99%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Amplification Coefficient of Error Terms. It is used to set
the S Curve.
Frequency Setting
Parameters
Frequency Command Lower Limit
Linear Number: P413
Default Value: 0
Minimum Value: -100
Maximum Value: 100
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the lower limit for Frequency Command.
Frequency Command Deadband Upper Limit
Linear Number: P414
Default Value: 10 pu
Minimum Value: 0 pu
Maximum Value: 100 pu
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the upper limit for Frequency Command Deadband.