76 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Digital Output #0 Logic
Linear Number: P301
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the logic for digital output #0.
Digital Output #0 Bit Selection
Linear Number: P302
Default Value: 0
Minimum Value: 0
Maximum Value: 15
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is used to select the bit (0...15) for digital output #0.
Digital Output #0 Delay
Linear Number: P303
Default Value: 0 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for digital output #0.
Digital Output #1 Memory Address
Linear Number: P304
Default Value: 99
Minimum Value: 0
Maximum Value: 500
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the memory address for digital output #1.
Value Description
0Non-Inverting
1Inverting