Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 173
Parameter Descriptions Chapter 2
Parameters Listed by Linear
Number
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
P007Number of Power Cells Per Phase0 9333344566689 OfflineYY
P008 Motor Rotation Direction Under Local
Control
0 1111111111111 OfflineYY
P009 Motor Rotation Direction Command
Selection
0 1000000000000 OfflineYY
P011 Power Cell DC Bus Rated Voltage 50 1300 650 650 920 920 848 848 976 920 920 976 976 976 V Offline Y Y
P012 Motor Rated Voltage 0 32767 2300 2400 3000 3300 4000 4160 6000 6300 6600 6900 10000 11000 V Offline Y Y
P013Motor Rated Power 0 32767000000000000kWOfflineYY
P014 Motor Rated Speed 0 5000 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 RPM Offline Y Y
P015 Motor Rated Power Factor 0 100 87.99 87.99 87.99 87.99 87.99 87.99 87.99 87.99 87.99 87.99 87.99 87.99 % Offline Y Y
P017Number of Motor Pole Pairs 0 100222222222222 Offline Y
P019 Encoder Resolution 0 4096 1024 1024 1024 1024 1024 1024 1024 1024 1024 1024 1024 1024 Offline Y
P024Stop Method 0 1000000000000 On/OffYY
P025Flux Reduction Enable 0 1000000000000 On/Off Y
P030 Powercell Fault Trip Signal Mask -32768 32767 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 Offline Y Y
P031 System Fault Trip Signal Mask -32768 32767 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 Offline Y Y
P034 Current Stability Loop Filter Time 0 32767 63 63 63 63 63 63 63 63 63 63 63 63 On/Off Y
P035 Current Stability Loop Frequency Range1
Output Scaling Factor
0 100 15 15 15 15 15 15 15 15 15 15 15 15 On/Off Y Y
P036 Current Stability Loop Output Upper
Limit
0 100 10 10 10 10 10 10 10 10 10 10 10 10 On/Off Y
P037 Current Stability Loop Output Lower
Limit
-100 100 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 On/Off Y
P038Current Stability Loop Enable 0 1000000000000 On/Off Y
P039 Current Stability Loop Enable Frequency
Range1 Upper limit
0 100 30 30 30 30 30 30 30 30 30 30 30 30 On/Off Y
P040Safe Start Condition 0 1111111111111 OfflineYY
P041Power Cell Bypass Enable 0 1000000000000 OfflineYY
P042 Power Cell Bypass Delay After Power Cell
Bypassed
20 16000 500 500 500 500 500 500 500 500 500 500 500 500 ms On/Off Y
P043 Power Cell Bypass Upper Limit For
Bypassed Feedback Time
30 500 100 100 100 100 100 100 100 100 100 100 100 100 ms On/Off Y

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals