102 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Low Voltage Ride Through System Delay Correction Factor
Linear Number: P288
Default Value: 999.76 μs
Minimum Value: -10000.00 μs
Maximum Value: 10000.00 μs
Access Level: R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the Low Voltage Ride Through System Delay Correction
Factor.
Low Voltage Ride Through Motor Speed Estimation Filter Time
Linear Number: P289
Default Value: 9.95 ms
Minimum Value: 0.98 ms
Maximum Value: 1000.00 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Offline Only
This parameter sets the Low Voltage Ride Through Motor Speed Estimation
Filter Time.
Power Loss Auto Restart
Parameters
Input Voltage Loss Filter Time
Linear Number: P073
Default Value: 0 ms
Minimum Value: 0 ms
Maximum Value: 1000 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Input Voltage Loss Filter Time.
Power Loss Restart Enable
Linear Number: P263
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is used to enable or disable the Power Loss Restart function.
Value Description
0Disable Power Loss Restart
1Enable Power Loss Restart

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals