Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 101
Parameter Descriptions Chapter 2
Low Voltage Ride Through Min Time Limit
Linear Number: P284
Default Value: 40 ms
Minimum Value: 10 ms
Maximum Value: 16383 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the minimum time lime for Low Voltage Ride Through.
Low Voltage Ride Through Max Time Limit
Linear Number: P285
Default Value: 1000 ms
Minimum Value: 10 ms
Maximum Value: 16383 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the maximum time limit for Low Voltage Ride Through.
Low Voltage Ride Through Recovery Frequency Compensation Factor
Linear Number: P286
Default Value: 0.00%
Minimum Value: -200.00%
Maximum Value: 199.99%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the Low Voltage Ride Through Recovery Frequency
Compensation Factor. 100% = 1 Hz * current frequency / rated frequency
Low Voltage Ride Through Recovery Time
Linear Number: P287
Default Value: 1500 ms
Minimum Value: 10 ms
Maximum Value: 16383 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the recovery time for Low Voltage Ride Through.