162 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Voltage Loop Parameters
Low Voltage Ride Through Parameters
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
P290Voltage Loop Enable 0 1111111111111 Offline Y
P296Current Feedback Filter Time 0 1000101010101010101010101010msOn/Off Y
P297Voltage Feedback Filter Time 0 1000101010101010101010101010msOn/Off Y
P298 Filter Time A For DC Bus Average Value 0 1000 100 100 100 100 100 100 100 100 100 100 100 100 ms On/Off Y
P299Filter Time B For DC Bus Average Value0 1000555555555555msOn/Off Y
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
P280 Low Voltage Ride Through Recovery
Voltage Boost Coefficient
0 100000000000000%On/Off Y
P281 Low Voltage Ride Through Min Time
Interval
0 1000101010101010101010101010sOn/OffYY
P282 Low Voltage Ride Through Min
Frequency Limit
5 100555555555555 OfflineYY
P283Low Voltage Ride Through Enable0 1111111111111 On/OffYY
P284 Low Voltage Ride Through Min Time
Limit
10 16383 40 40 40 40 40 40 40 40 40 40 40 40 ms Offline Y
P285 Low Voltage Ride Through Max Time
Limit
10 16383 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 ms Offline Y
P286 Low Voltage Ride Through Recovery
Frequency Compensation Factor
-200.00 199.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Offline Y
P287 Low Voltage Ride Through Recovery
Time
10 16383 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 ms Offline Y
P288 Low Voltage Ride Through System Delay
Correction Factor
-10000.00 10000.00 999.76 999.76 999.76 999.76 999.76 999.76 999.76 999.76 999.76 999.76 999.76 999.76 μs Offline Y
P289 Low Voltage Ride Through Motor Speed
Estimation Filter Time
0.98 1000.00 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 9.95 ms Offline Y

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals