Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 107
Parameter Descriptions Chapter 2
Bypass Mode Switch 
Parameters
Bypass Mode Selection
Linear Number: P484
Default Value: 0
Minimum Value: 0
Maximum Value: 4
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is used to select the Bypass Mode.
Fault Automatic Switch to 
Bypass Parameters
Fault-To-Bypass
Linear Number: P471
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is used to enable or disable the Fault-To-Bypass function.
Fault-To-Bypass Delay
Linear Number: P472
Default Value: 3 s
Minimum Value: 0 s
Maximum Value: 5 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the time delay to enable the bypass after the drive faults. This 
is only used when Fault-To-Bypass (P471) is set to ‘1’ and Bypass Mode Selection 
(P484) is set to ‘2’.
Value Description
0No Bypass
1 Manual Bypass, One-drive-one-motor
2 Automatic Bypass, One-drive-one-motor
3Manual Bypass, One-drive-two-motor
4 Automatic Bypass, One-drive-two-motor
Value Description
0Disable Fault-To-Bypass
1Enable Fault-To-Bypass