Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 9
Chapter 1
Functional Descriptions
Introduction
The PowerFlex 6000 is an adjustable speed AC drive that is particularly suitable 
for new and retrofit centrifugal fan and pump applications. Air-cooled PowerFlex 
6000 drives are designed to maximize energy efficiency by enabling soft-starting 
and variable-speed control in medium voltage, normal duty applications.
To achieve the low input harmonics and near-unity power factor that make this 
an ideal solution for standard motors, the drives utilize Cascaded “H’” Bridge 
(CHB) topology. This proven CHB topology combines an integrally mounted 
phase-shifting isolation transformer with series-connected power modules for 
each phase. In addition to stepping down the input voltage, the isolation 
transformer also provides two other principal functions:
• Mitigate common mode voltage stress so motors with standard insulation 
levels can be used.
• Reduce Total Harmonic Distortion (THD), due to the phase shifting of 
its secondary windings, so input side harmonics don’t negatively impact 
the plant or utility power grid.
System Settings
The system settings include the following functions:
• Control Owner
 on page 10
• HMI Display on page 12
• Nameplate on page 13
• Ramp on page 14
• Rated Frequency on page 15
• Stop Mode on page 15
• Motor Direction Control on page 16
• Switch Frequency Settings on page 16
• Tre n d s  on page 17
• VF Curve Setting on page 17