168 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Skip Frequency Parameters
Start and Stop Sequence Parameters
Deceleration and Acceleration Parameters
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
P089Skip Frequency Enable 0 1000000000000 On/OffYY
P090Skip Frequency 1 Lower Limit 0 75000000000000 On/OffYY
P091Skip Frequency 1 Upper Limit 0 75000000000000 On/OffYY
P092Skip Frequency 2 Lower Limit 0 75000000000000 On/OffYY
P093Skip Frequency 3 Upper Limit 0 75000000000000 On/OffYY
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
P447Minimum Start Frequency During Time0 13.650000000000000sOfflineYY
P448Minimum Start Frequency 0 10000000000000%OfflineYY
P449 Low Speed Voltage Compensation
During Flux Building Process
0 3222222222222%OfflineYY
No. Name Min. Max. Default Values Units Modify
Root
Access
2300V 2400V 3000V 3300V 4000V 4160V 6000V 6300V 6600V 6900V 10000V 11000V U S R
P385Deceleration Process Enable 0 1000000000000 OfflineYY
P386 Deceleration Time 1 1.0 3276.7 150.0 150.0 150.0 150.0 150.0 150.0 150.0 150.0 150.0 150.0 150.0 150.0 s On/Off Y Y
P387 Deceleration Frequency 1 0 75 30 30 30 30 30 30 30 30 30 30 30 30 On/Off Y Y
P388 Deceleration Time 2 1.0 3276.7 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 s On/Off Y Y
P389 Deceleration Frequency 2 0 75 20 20 20 20 20 20 20 20 20 20 20 20 On/Off Y Y
P390 Deceleration Time 3 1.0 3276.7 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0 s On/Off Y Y
P391 Deceleration Frequency 3 0 75 10 10 10 10 10 10 10 10 10 10 10 10 On/Off Y Y
P392 Deceleration Time 4 1.0 3276.7 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 s On/Off Y Y
P418 Acceleration Time 1 1.0 3276.7 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 s On/Off Y Y
P419 Acceleration Frequency 1 0 75 10 10 10 10 10 10 10 10 10 10 10 10 On/Off Y Y

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals