136 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
VFD Overload Current Offset
Linear Number: P107
Default Value: 4.99%
Minimum Value: 0.00%
Maximum Value: 399.99%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the overload current offset for the drive.
Motor Overload Current Offset
Linear Number: P108
Default Value: 4.99%
Minimum Value: 0.00%
Maximum Value: 399.99%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the overload current offset for the motor.
Heating Current Threshold
Linear Number: P110
Default Value: 110.00%
Minimum Value: 0.00%
Maximum Value: 399.99%
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the drive heating current.
Line Over Voltage Fault Threshold
Linear Number: P154
Default Value: 115.00%
Minimum Value: 0.00%
Maximum Value: 199.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the input over voltage fault.