Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 137
Parameter Descriptions Chapter 2
Line Over Voltage Fault Delay
Linear Number: P155
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the input over voltage fault.
Line Under Voltage Warning Threshold
Linear Number: P156
Default Value: 80%
Minimum Value: 0%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the input under voltage warning.
Line Under Voltage Warning Delay
Linear Number: P157
Default Value: 1000 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the input under voltage warning.
Line Neutral Over Voltage Warning Threshold
Linear Number: P158
Default Value: 60.00%
Minimum Value: 0.00%
Maximum Value: 199.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the ground input over voltage warning.