138 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Line Neutral Over Voltage Warning Delay
Linear Number: P159
Default Value: 1000 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the ground input over voltage warning.
Line Neutral Over Voltage Fault Threshold
Linear Number: P160
Default Value: 80.00%
Minimum Value: 0.00%
Maximum Value: 199.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the threshold for the ground input over voltage fault.
Line Neutral Over Voltage Fault Delay
Linear Number: P161
Default Value: 1000 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay for the ground input over voltage fault.
Line Voltage Positive Sequence Filter Time
Linear Number: P162
Default Value: 10 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the time for the Line Voltage Positive Sequence Filter.