68 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Frequency At Second Point for 5 Point VF
Linear Number: P377
Default Value: 20%
Minimum Value: 10%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the Frequency At Second Point for 5 Point VF.
Amplitude At Second Point for 5 Point VF
Linear Number: P378
Default Value: 10%
Minimum Value: 0%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the Amplitude At Second Point for 5 Point VF.
Frequency At Third Point for 5 Point VF
Linear Number: P379
Default Value: 40%
Minimum Value: 10%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the Frequency At Third Point for 5 Point VF.
Amplitude At Third Point for 5 Point VF
Linear Number: P380
Default Value: 27%
Minimum Value: 0%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter sets the Amplitude At Third Point for 5 Point VF.