84 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
K Number 252
Access Level: R&D
Read/Write: Read only
This register stores the value of the actual frequency. The unit is PU.
Analog Output #1 Filter Time
Linear Number: P333
Default Value: 1000 ms
Minimum Value: 0 ms
Maximum Value: 32767 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the filter time for analog output #1.
Analog Output #1 Offset
Linear Number: P334
Default Value: 0 pu
Minimum Value: -100 pu
Maximum Value: 100 pu
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the offset for analog output #1.
Analog Output #1 Scaling Factor
Linear Number: P335
Default Value: 100.00%
Minimum Value: 0.00%
Maximum Value: 199.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the scaling factor for analog output #1.
Analog Output #2 Memory Address
Linear Number: P336
Default Value: 206
Minimum Value: 0
Maximum Value: 500
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the memory address for analog output #2.