Install and Connect MCC1 (Multicarrier) Cabinet
Connect AC Power and Ground
334 SI Installation and Upgrades
June 2004
Connect AC Power and Ground
Return to Task List
CAUTION:
The equipment room AC power and ground wiring must be performed by a qualified
electrician. Refer to the Hardware Guide for Avaya Communication Manager (555-245-
207) for site requirement information.
CAUTION:
The power circuit must be dedicated to the system and must not be shared with other
equipment and must not be controlled by a wall switch. The AC receptacle should not be
located under the MDF.
CAUTION:
System grounding must comply with the general rules for grounding contained in Article
250 of the National Electrical Code (NEC), National Fire Protection Agency (NFPA) 70,
or the applicable electric code in the country containing the equipment. For more
information, refer to Approved Grounds
.
For information about connecting AC power and ground, see:
Power Requirements
Power Supply Sources (J58890CE-1, J58890CE-2, and J58890CH-1)
Grounding an AC-Powered System (J58890CE)
Connect Mixed AC/DC Power and Ground