EasyManua.ls Logo

BRUEL & KJAER VIBROCONTROL 8000 - 16.1.8 X (Tracking Filter); 16.1.9 Clamp & 2 mA Clamp

BRUEL & KJAER VIBROCONTROL 8000
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 114 of 188
© Brüel & Kjaer Vibro S1079330.002 / V04
Technical alterations reserved
EN
16.1.8 X (Tracking Filter)
The X column sets the tracking filter for the measurement (when applicable). Tracking filters can be
set from 0.01 to 15.99. A radial vibration measurement has two standard tracking filter measurements
(1X, and 2X). A tracking filter includes both an amplitude and a phase measurement.
To change (for example) the existing 2X tracking filter to 0.5X, simply edit the X field (from 2 to 0.5).
Don’t forget to also change the measurement name from 2X Amplitude to 0.5X Amplitude.
Figure 16-4) Modify nX tracking filter
16.1.9 Clamp & 2 mA Clamp
The Modbus output values will clamp (freeze) to this scaling value when the channel is bypassed or
faulted. The default value is 0 (i.e. 0 mils pp)
The Analog value will also clamp to this value when the channel is bypassed or faulted. If the clamp
value is 0 (i.e. 0 mils pp) the output will clamp to 4 mA. If 2mA Clamp is enabled the analog output will
clamp to 2 mA.
Example 1: Radial Vibration channel, Scale = 0-10 mils pp, Clamp = 0 (0 is at bottom scale). If the
channel goes Not OK, Modbus will send 0 mils pp. The analog output will be 4 mA.
Example 2: Axial channel, Scale = -40 to 0 to +40 mils, Clamp = 0 (0 is at midscale). If the channel is
bypassed the Modbus value will send 0 mils. In Modbus scaled data (i.e. 0-65535) midscale is 32767
(0 mils). For the analog signal midscale is 12 mA.
The default clamp value is 0. It is rarely changed.

Table of Contents