EasyManua.ls Logo

BRUEL & KJAER VIBROCONTROL 8000 - 9.5.1 4-20 mA Fault Conditions; 9.5.2 4-20 mA Output Wiring

BRUEL & KJAER VIBROCONTROL 8000
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 64 of 188
© Brüel & Kjaer Vibro S1079330.002 / V04
Technical alterations reserved
EN
9.5.1 4-20 mA Fault Conditions
In the event of a sensor fault, the 4 to 20 mA output will drop to bottom scale (4 mA). This value is
configurable in the MPS Setup software. A 2 mA clamp option is also available for faulted channels.
An output between 20 mA and 24 mA indicates an over-range condition.
9.5.2 4-20 mA Output Wiring
The maximum cable length is a function of the supply voltage and the total loop resistance as shown
in Figure 9-14.
Figure 9-14) Analog Output Maximum Loop Resistance
The total loop resistance includes the sensing load and the total wire resistance. For wire runs longer
than 1,500 m (5,000 ft.) 24 AWG is the minimum recommended wire size. Use 20 AWG wire for runs
up to 3,000 m (10,000 ft.). Above 3,000 m (10,000 ft.) the cable capacitance may limit frequency
response. Consult with Brüel & Kjær Vibro if you need analog output wiring runs longer than 3,000 m
(10,000 ft.)
Shielded wire is recommended to reduce electrical noise. Terminate shielding at the receiving
device.

Table of Contents