© Brüel & Kjaer Vibro ● S1079330.002 / V04 ● █ Page 31 of 188
Technical alterations reserved!
Brüel & Kjaer Vibro │ Instruction
VC-8000 MPS
Content
EN
3.6 Mounting Hole Drawings
For mounting hole drawings please visit the downloads page on the B&K Vibro website.
3.7 Other Considerations
3.7.1 Mounting the Display Remotely
You can mount the touch screen display
(like on a door) up to 10 feet (3.0 m) from
the rack. Secure the display cable every
6” (15 cm).
A rack mounted display can be modified
in the field to be remote mounted. A
longer display cable will be needed.
See the datasheet for part numbers and
ordering information for the remote
display.
See Drawing 1109209 on the B&K Vibro
website for cut-out dimensions for the
remote display.
Figure 3-6) Display mounted remotely
3.7.2 Clearance and Cooling
VC-8000 racks require 4” (100 mm) of
clearance between the rack and any other
component. This clearance provides
proper airflow for cooling.
When modules are wired from the front of
the rack, it is common to find racks with
wires laying on top of the rack and
blocking the airflow through the rack.
Please use wiring harnesses etc. to keep
the airflow open around the rack.
Figure 3-7) Clearance (inch)