© Brüel & Kjaer Vibro ● S1079330.002 / V04 ● █ Page 155 of 188
Technical alterations reserved!
Brüel & Kjaer Vibro │ Instruction
VC-8000 MPS
Content
EN
23.5 Event Lists
The following entries can appear in the VC-8000 System Event List.
The event list can be viewed from the Touch Panel display or by connecting to the rack with a laptop
running the VC-8000 Maintenance software.
Event Name Description Recommended Actions
Trip Multiply is enabled.
Latched Statuses Reset
The reset contact (or button) was activated.
Special Alarm Inhibit is enabled.
The channel is in bypass.
Critical Hardware Failure
The module has failed a critical self-test.
Module Rebooted
The module processor has reset.
Configuration Slot does
not match Actual Slot
The slot number (software) does not match the
physical location of the module. Operation is
configuration to the monitor.
Channel Fault (Not OK)
Transducer signal is faulted
Check the sensor field wiring
Module Inserted into
A module has been inserted into the system.
Module Removed from
A configured module has been removed from the
system.
DCS Link Failure
The VC-8000 is not receiving Modbus queries.
Verify Modbus connections.
Table 23-4) System Event Events
23.6 Inserting and Removing Modules
You may remove VC-8000 Modules while the system is powered (Hot Swap). Remember that every
VC-8000 UMM/TMM card has relay channels.
Before removing cards:
• Make sure the rack (all trips) are externally bypassed.
• Notify operators that VC-8000 channel statuses will become invalid and the Fault relay will
activate.
Before installing cards:
• Verify the card is not upside down. The card will fit into the slot upside down, but will not seat
into the backplane. If you push hard to force the card to seat, the connector on the card may
break.
VC-8000 Modules can be damaged by electrostatic shock when removed from the rack. Take
appropriate precautions such as grounding straps.