12.2.3 Asset level 1 & Asset Level 2 Groups
Asset 1 and Asset 2 are used to help organize, identify,
and group channels.
Asset names have multiple uses in the VC-8000 system.
Asset names are used to organize the Machine
view display (see 12.2.3.1).
Asset names are used in the VC-8000 event list
to indicate the source of the alarm.
Asset names are used in the relay logic blocks
(Figure 12-9) Asset Level 1 used in relay logic).
This is very convenient, but you must recognize
that if the groups change so does your relay
logic.
Asset names are not used in CMS software. The
CMS software uses the “CMS Navigation Path”.
For large machines, Asset 1 is typically the machine
group (i.e. Turbine, or Compressor). Asset 2 is typically
the bearing group (i.e. Brg 1, Brg 2, etc.)
For smaller machines, Asset 1 is typically the machine
train name (MP-1211, MP-1222) and Asset 2 is the
machine name (Motor, Pump). Use the strategy that best
works for you.
Figure 12-8) Asset Level 1 & 2 group
names
Figure 12-9) Asset Level 1 used in relay logic