EasyManua.ls Logo

BRUEL & KJAER VIBROCONTROL 8000 - 7.2.5 Using Plant-Wide +24 Vdc Power; 7.2.6 Designating a “Primary” Power Supply; 7.2.7 Power Redundancy (Do I need a PCM?); 7.2.8 Power Wiring Cable Lengths

BRUEL & KJAER VIBROCONTROL 8000
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 42 of 188
© Brüel & Kjaer Vibro S1079330.002 / V04
Technical alterations reserved
EN
7.2.5 Using Plant-Wide +24 Vdc Power
Occasionally a site will have a main +24 Vdc line that is used by all +24 Vdc devices. In this case a 24
Vdc isolator would be required for the VC-8000 rack.
The isolator is needed because the VC-8000 rack power common is the same as the UMM common;
and connecting the plant-wide +24 Vdc to the RCM may cause a ground fault. If this is your scenario
the site/plant may simply prefer for you to use a standard power supply (i.e. 120-230 Vac to
+24 Vdc) rather than using an isolator.
IMPORTANT
The rack power connector (COM terminal) is not isolated from UMM signal COM. When using
plant-wide (+24 Vdc) power, a 24 V to 24 V isolator will be necessary (BKV #100549)
7.2.6 Designating a “Primary” Power Supply
The VC-8000 draws power from the power supply with the highest (in specification) voltage. To
prefer a primary supply over a secondary (redundant) supply, adjust the voltage of the primary supply
to be 1 V higher than the secondary.
7.2.7 Power Redundancy (Do I need a PCM?)
Power supply redundancy is external to the rack. The (single) RCM distributes the power from the two
redundant power supplies.
The PCM card was designed (rare cases) as a temporary backup power source when an RCM needs
to be replaced without losing power to the rack. A blank slot would be required to install the PCM. The
PCM is not designed as a permanent redundant power card.
7.2.8 Power Wiring Cable Lengths
The following table shows the maximum wire length for fully loaded racks when powered with a +24
Vdc power supply.
Wire Size 16P Rack 8P Rack 4P Rack
12 AWG
23 m (75 ft.)
61 m (200 ft.)
104 m (340 ft.)
14 AWG
18 m (50 ft.)
46 m (150 ft.)
76 m (250 ft.)
16 AWG
9 m (30 ft.)
24 m (80 ft.)
41 m (135 ft.)
18 AWG
6 m (20 ft.)
16 m (50 ft.)
26 m (85 ft.)
Table 7-2) Maximum Power Wire Length at +24 Vdc Input Power

Table of Contents