EasyManua.ls Logo

BRUEL & KJAER VIBROCONTROL 8000 - 8.2.2 Wiring Thermocouples

BRUEL & KJAER VIBROCONTROL 8000
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 50 of 188
© Brüel & Kjaer Vibro S1079330.002 / V04
Technical alterations reserved
EN
8.2.2 Wiring Thermocouples
Wire thermocouples as shown. The VC-8000 isolates thermocouple common lines; this allows
connection to grounded tip thermocouples. All thermocouple inputs share the same common plane,
so grounded tip thermocouples should be at the same ground potential.
Figure 8-11) Thermocouple wiring
Type
ANSI/ASTM E-230 Color Coding IEC 584-3 Color Coding
B Terminal (+) C Terminal (-) B Terminal (+) C Terminal (-)
J
White
Red
Black
White
K
Yellow
Red
Green
White
T
Blue
Red
Brown
White
E
Violet
Red
Violet
White
Table 8-2) - Thermocouple color coding