21.6.4 Read System Status Registers
The System registers are for customers using the SETPOINT PI/XC Adapter and the CMS software.
The register that is commonly used is “Adapter Overall”.
There are two groups of System status registers. The first group indicates a “Data Link Fault”. The
second group indicates “Full”
21.6.4.1 Data Link Fault
The registers can be used to notify operations of a fault in the CMS system. Typically, only the
‘Adapter Overall’ status would be used by the customer.
Register Description
Data Format
Typical
Adapter Overall
SETPOINT PI/XC Adapter not communicating (general)
X
Rack to Adapter
PI/XC Adapter not communicating to rack
AF to Adapter
PI/XC Adapter not communicating to AF Server
Backup (XC)
XC Data is not being saved
SD Card
SD card is not storing data
HD
HD Memory is not storing data
Modbus
Modbus data is not being read
21.6.4.2 Full
The registers can be used to notify operations of a fault in the CMS system.
Register Description
Data Format
Typical
Adapter Overall
Don’t use
Rack to Adapter
Don’t use
AF to Adapter
Don’t use
Backup
XC hard drive is full
SD Card
SD Card is full
HD
HD (SAM) is full
Modbus
Don’t use
21.6.5 Bit Packing (Status) into 16 bit Registers
If needed, the status bits can be packed into 16-bit registers. These registers would then be accessed
via the Holding registers (4x) or the Input registers (3x).
The standard map only uses coil or discrete input address range and Bit is always set to “1”.
Figure 21-7) Address and bit settings for individual status registers