EasyManua.ls Logo

BRUEL & KJAER VIBROCONTROL 8000 - Wiring - Interfacing to External Systems (DCS)

BRUEL & KJAER VIBROCONTROL 8000
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© Brüel & Kjaer Vibro S1079330.002 / V04 Page 53 of 188
Technical alterations reserved!
Brüel & Kjaer Vibro Instruction
VC-8000 MPS
Content
EN
9 Wiring - Interfacing to External Systems (DCS)
There are many features in the VC-8000 hardware designed specifically to interface to the DCS or
other external systems. Some are for sharing information, others allow a measure of control. This
section provides some guidelines on how best to use these interfaces.
9.1 Modbus Connections and Wiring
The Modbus communications link allows the VC-8000 to
send data and status to a DCS (for example) for operator
viewing screens. This communication link is very common
and highly recommended.
Two Modbus ports are available on the SAM module. The
Modbus TCP (Ethernet) port, as well as a Serial (RS-
232/RS-422/485) port.
Modbus provides measurements and statuses to a control
system. Modbus does not provide waveform data (i.e.
orbits, spectra).
If you were to see a full list of the Modbus data available
from the rack it would be a little overwhelming. Typically,
only a small fraction of the available data is shared with
other systems. The table below shows examples of data
that is commonly read from the rack.
Figure 9-1) SAM Modbus
Connectors
Modbus Data Register Type Example Register
Channel value
32-bit (or 16-bit)
30001
Channel Fault
Status bit
10001
Channel in Alert
Status bit
10002
Channel in Danger
Status bit
10003
Rack Power Supply 1
Status bit
10004
Rack Power Supply 2
Status bit
10005
CMS Data Collection Ok
Status bit
12955
Table 9-1) Typical Modbus registers read by DCS

Table of Contents