17.4.3 Deleting a Block
To delete a block, select the block and select delete on your keyboard.
To delete a connector, select the connector at the input to the block
and select delete on your keyboard.
17.4.4 Configuring DPDT Pairs
Sometimes it is necessary to trip two relays instead of one. To trip two relays, simply connect a
second relay to the logic output as shown in Figure 123. This simulates a Double-Pole, Double-Throw
(DPDT) relay output by driving two Single-Pole, Double-Throw relays from the same logic output.
Figure 17-13) DPDT configuration
17.4.5 Group Line Limitation
The VC-8000 system has 16 “group lines” that provide voting across multiple monitors. Please see
section 4.3 for more information.
17.4.6 Viewing the Summary
To see a summary chart of the relay configuration,
select Summary from the view drop list as shown
in Figure 17-4.
Figure
17-12) Delete connector
Figure
17-14) Relay Summary view