23.11.2 Bypass Relay Channel
Relay Bypass forces the relay into the non-alarm state, regardless of any alarm conditions in the rack.
Use the VC-8000 Maintenance software to bypass relays; the Maintenance display on the touch
screen panel cannot bypass relays.
To bypass a relay, follow these steps
Action Screen Capture
Select the relay channel.
Although all four relay channels are shown,
Slot 3 Channel 1 (Motor High Vib) is the
selected channel.
Select Enable Bypass.
Enter password (if required).
Confirm.
Slot 3, channel 1 (Motor High Vib) is bypassed.
Notice that channel 2 is still active.
Select close to return to the main screen.