EasyManua.ls Logo

BRUEL & KJAER VIBROCONTROL 8000 - 7.2.2 Input Power Fuse Protection; 7.2.3 Power Status (LEDs); 7.2.4 Selecting an External Power Supply

BRUEL & KJAER VIBROCONTROL 8000
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© Brüel & Kjaer Vibro S1079330.002 / V04 Page 41 of 188
Technical alterations reserved!
Brüel & Kjaer Vibro Instruction
VC-8000 MPS
Content
EN
7.2.2 Input Power Fuse Protection
The RCM includes power input fuse protection and reverse wiring protection. The fuse is not
replaceable. All other power supply voltages and conditioning circuits are distributed on the SAM and
monitoring modules.
7.2.3 Power Status (LEDs)
The RCM has two LEDs that indicate power status. Refer to section 23.3.1 for information on
troubleshooting if the LEDs are not as shown.
LED
Normal Condition
Description
P1
On (Green)
Power 1 is between +18 and +36 Vdc.
P2
On (Green)
Power 2 is between +18 and +36 Vdc.
Table 7-1) RCM LED States
You can monitor the status of the power supplies through Modbus.
7.2.4 Selecting an External Power Supply
The amount of power required varies greatly depending on the number (and loading) of the
monitoring modules. The power supply wattages (from the MPS datasheet) shown here, will handle
fully filled and fully loaded racks for the size given.
480 W supply for a 16P rack
180 W supply for an 8P rack
90 W supply for a 4P rack
See the RCM data sheet (S1078950) for more information on the external power supplies provided by
B&K Vibro.
ELECTRICAL SHOCK HAZARD
The external power supplies are powered from hazardous high voltages. Only qualified
personnel should make connections to the power supply.
See safety instructions included with
the power supply module.

Table of Contents