l Stop bits
Setsthenumberofstopbits,wherebythedefaultsettingis1.
Displayed information
BelowtheUARTsettingsaretheconnectionproperties(Hardware:RS485or
RS232/Port:13).
PROFIBUS settings
Delphin devices are set to address 126 via the web
interface in factory mode or after configuration reset
(default configuration). This address is a placeholder
and does not exist in the PROFIBUS network.
PROFIBUS address
Slave address:EntertheaddressconfiguredinPROFIBUSmasterforthedevice(1
to125).
Displayed information
Theconnectionproperties(Hardware andPort )aredisplayedbelowthePROFIBUS
settings.
Thesymbol isthendisplayedforthechannelfollowingconfiguration.Then
createandconfiguretherequiredPROFIBUSchannels(Signals).
PROFIBUS logger settings
PROFIBUS baud rate
Baud rate:EnterthebaudrateoftheconnectedPROFIBUSnetworkhere.
Displayed information
Theconnectionproperties(Hardware andPort )aredisplayedbelowthePROFIBUS
settings.
Thesymbol isthendisplayedforthechannelfollowingconfiguration.Then
createandconfiguretherequiredPROFIBUSloggerprotocol.
Othersettingsaredescribedinthefollowingsections:
l PROFIBUSprotocol
l PROFIBUSchannel
l PROFIBUSloggerprotocol