4 Basic Instructions
DVP-20PM Application Manual
4-9
Instruction
code
Function Applicable model
20PM
TMR
16-bit timer
T-K T0~T255, K0~K32,767
Operand
T-D T0~T255, D0~D9,999
Explanation
When the instruction TMR is executed, the coil specified is ON, and the timer
specified begins to count. If the timer value matches the setting value (timer
valuesetting value), the contact specified will act in the way described below.
NO (Normally-open) contact OFF
NC (Normally-closed) contact ON
Example
Ladder diagram:
X0
T5TMR
K1000
Instruction code: Description:
LD X0 Loading the Form A
contact X0
TMR T5 K1000
The setting value in
the timer T5 is
K1000.
Additional
rema
rk
Please refer to the specifications for the model used for more information about
the timer range which can be used.
Instruction
code
Function Applicable model
20PM
CNT
16-bit counter
C-K C0~C199, K0~K32,767
Operand
C-D C0~C199, D0~D9,999
Explanation
When the counter coil specified by the instruction CNT is turned from OFF to
ON, the counter value increases by 1. If the counter value matches the setting
value (counter value=setting value), the contact specified will act in the way
described below.
NO (Normally-open) contact OFF
NC (Normally-closed) contact ON
If there are pulses sent to the counter specified by the instruction CNT after the
counter value matches the setting value, the state of the contact specified and
the counter value will remain unchanged. Users can reset a counter by means
of the instruction RST.
Example
Ladder diagram:
X0
C20CNT
K100
Instruction code: Description:
LD X0 Loading the Form
A contact X0
CNT C20 K100
The setting value
in the counter
C20 is K100.