5 Applied Instructions and Basic Usage 
Example 2
 
  A DVP-20PM series motion controller is connected to a VFD-B series AC 
motor drive (RTU mode: M1143=ON) 
Processing the data received
 Communication protocol: 9600,8,E,1
The communication protocol set is retained.
Communication timeout: 100 ms
M1127 is reset.
Request for sending data
The data received is stored in D1070~D1085 
in the form of hexadecimal values. 
Communication command:
Device address: 01
Data address: H2000
Data:H12
The reception 
of data is complete.
M100
MOV H87 D1120
SET
M1120
SET
M1143
MOV
K100 D1129
RST
M1127
M1127
X0
MODWR K1
H2000
H12
SET
M1122
X1
RTU mode
 
DVP-20PM series motion controller  VFD-B series AC motor drive: The 
DVP-20PM series motion controller sends “01 06 2000 0012 02 07”. 
VFD-B series AC motor drive  DVP-20PM series motion controller: The 
DVP-20PM series motion controller receives “01 06 2000 0012 02 07”. 
Data transmission registers in the DVP-20PM series motion controller 
(message sent by the DVP-20PM series motion controller): 
Register  Data  Description 
D1089 low  01 H  Address 
D1090 low  06 H  Function 
D1091 low  20 H 
D1092 low  00 H 
Data address 
D1093 low  00 H 
D1094 low  12 H 
Data 
D1095 low  02 H  CRC CHK Low 
D1096 low  07 H  CRC CHK High 
Data reception reigsters in the DVP-10PM series motion controller (message 
with which the VFD-B series AC motor drive responds): 
Register  Data  Description 
D1070 low  01 H  Address 
D1071 low  06 H  Function 
D1072 low  20 H 
D1073 low  00 H 
Data address 
D1074 low  00 H 
D1075 low  12 H 
Data content 
D1076 low  02 H  CRC CHK Low 
D1077 low  07 H  CRC CHK High 
 
DVP-20PM Application Manual 