5 Applied Instructions and Basic Usage
DVP-20PM Application Manual
5-162
Output pin
Name Function
Data
type
Time when there is
a transition in an
output pin’s signal
from low to high
Time when there is a transition in an
output pin’s signal from high to low
Aborted
The execution of
the motion
control function
block is
interrupted by a
command.
BOOL
The execution of
the motion control
function block is
interrupted by a
command.
There is a transition in the Aborted
output pin’s signal from high to low
when there is a transition in the
Execute input pin’s signal from
high to low.
If the Execute input pin is set to
False when the execution of the
motion control function block is
interrupted, the Aborted output pin
will be set to False in the next
cycle.
Error
An error occurs in
the motion
control function
block.
BOOL
Input values are
incorrect.
The axis specified
is in motion before
the motion control
function block is
executed.
There is a transition in the Error
output pin’s signal from high to low
when there is a transition in the
Execute input pin’s signal from
high to low.
The number of pulses is a unit for the Position1 input pin/the Position2 input pin, and the number of
pulses per second is a unit for the Velocity1 input pin/the Velocity2 input pin. Users can change the unit
used by means of the motion control function block T_AxisSetting2.
3. Troubleshooting
Error Troubleshooting
The values of input pins in the motion control function
block are incorrect.
Check whether the values of the input pins are in the
ranges allowed.
The motion control function block conflicts with other
motion control function blocks.
Make sure that other uniaxial motion control function
blocks are not started or the execution of other
uniaxial motion control function blocks is complete
before the motion control function block is started.
4. Example
Purposes:
The motion control function block T_AbsSeg2 is used to start absolute two-speed motion of an axis.
The first motion is set so that the first axis moves at a speed of 2,000 pulses per second, and
moves for 10,000 pulses. The second motion is set so that the first axis moves at a speed of 3,000
pulses per second, and moves for 15,000 pulses.