Page 152 • 700120S • ENTRON Controls, LLC.
Weldsafe 5000 Data Sheet • Circuit Savers • phone: (972) 370-0664 • www.circuitsavers.com • March 10, 2006
Legend
H1 LED green POWER ON
H2 LED red GROUND FAULT
H3 LED red CT FAULT
H4 LED red LOOP RESISTANCE > 1
H5 LED red CRUSH FAULT
H6 LED red VOLTAGE BUILD-UP
K1 Ground fault alarm relay
K2 Ground check alarm relay
S1 Internal test button
S2 Internal reset button
S3 Switch for ground fault Failsafe/Active
(behind front cover)
Closed=active Open=failsafe
S4 Switch for ground check Failsafe/Active
(behind front cover)
Closed=active Open=failsafe
S5 External test button
S6 External reset button for ground fault sensing
S7 External reset button for ground checking
S8 Trip level adjustment (behind front cover)
Closed = 10 mA fixed, factory setting
Open = 10 mA inverse response
**R1 Loop resistance adjustment - see instructions L
PLEASE NOTE:
TO CHECK UNIT FUNCTION
DURING COMMISSIONING, WE
RECOMMEND TESTING THE
Weldsafe 5000 UNDER TRUE
FAULT CONDITIONS. FOR THE
GROUND FAULT FUNCTION, A
SMALL RESISTOR, (e.g. 30 K
AT
480V WILL GENERATE APPROX.
16 mA) CAN BE USED TO CREATE
THIS CONDITION. FOR THE
GROUND CHECKING FUNCTION,
OPEN THE PILOT WIRE.
Terminals
2-3 Input power supply 120V ac or 24 V ac
+/-15%
8-9-10 Contact for K1 alarm relay – ground
fault
12-13-14 Contact for K2 alarm relay – ground
check
16-17 C.T. connection
18-19 Ground fault external reset,
Hand=closed Auto=open
22-23 External test button (optional)
25-26 Ground check external reset,
Hand=closed Auto=open
27 Pilot wire if using standard ground
check monitoring
29 Pilot wire if using EOL monitoring
30 Ground connection
EOL End-of-line resistor, 49.9, +/-0.1
L **R1 Loop Resistance Adjustment
This is an internal adjustment that must
made when cable length is very long and
the loop resistance is high (0.5..0.8).
Please check with manufacturer about your
specific application.
Weldsafe 5000 combination ground fault sensing and ground checking relay
S8 S3
APPENDIX D WELDSAFE 5000 (cont.)
S4